What is Cooling Load? Purpose & Calculation - ElectricalWorkbook (2022)

Cooling load is defined as, “the total heat required to be removed from the space in order to bring it to the desired temperature by air conditioning and refrigeration equipment”.

Purpose of cooling load estimation: To determine the size or capacity of air conditioning and refrigeration equipment, which is required to maintain desired inside conditions during theperiod of high temperatures.The design load is based on inside and outside design conditions. It is responsibility of ‘Air conditioning and Refrigeration Equipment Capacity’ to maintain the desired inside conditions.

Calculation of Cooling Load

The two main components of a cooling load are, (l) Sensible heat load and (2) Latent heat load.

Sensible heat load:

Different factors/sources of sensible heat load are :

Heat flow due to conduction, through exterior walls, floors, ceiling, doors, and windows due to temperature difference in the two sides:

U = Overall heat transfer coefficient,

A = Area of wall,

δT = Temperature difference between inside and outside

The heat flow is calculated as,

Q = Total heat transfer = U × A × δT

Heat flow due to solar radiation:

(Video) CoolingLoad

It consists of,

Heat transmitted through glass of Windows and doors

When a sheet of glass is subjected to solar radiation, a part of solar radiations incident on glasssurface is reflected and the remaining part is transmitted directly into the interior of building.

Q = Total heat transfer = U × A × δT

Heat absorbed by walls and roofs exposed to solar radiation

It is calculated as,

Q = Total heat transfer = U × A × δT

Heat Gain to the space or room to be conditioned due to ventilation

This heat load is also called as “ventilation load”. The ventilation (i.e. supply of outside air) is provided to the conditioned space in order to minimise odour, concentration of smoke, carbon dioxide and other undesirable gases, so that, freshness of air could be maintained. The quantity of outside air used for ventilation should provide at least one-half air change per hour in buildings having normal ceiling heights. Also, if the infiltration air quantity is larger than the ventilation quantity, then the quantity of ventilation should be increased to at east equal to the quantity of infiltration air. This outside air adds sensible as well as latent heat.

Heat brought through leakage and infiltration OR Infiltration load:

The infiltrated air is the air, Which enters a conditioned space through Window cracks andopening of doors. This is caused due to the pressure difference between the room and the ambient pressure.Infiltration is also a function of wind velocity and density variation of air due to temperature difference between inside and outside air.There are two methods of estimating the infiltrated air.

(i) Crack length method (ii) Air change method.

(Video) Hap tutorial 1, cooling load calculation of a building | HVAC 01

In most of the cases, air change method is used. According to it, Quantity of infiltrated air through Windows and wall = (L × W × H × A)/60 in m3/min

Lightening load / Appliances load:

The appliances frequently used in air conditioned space may be electrical, gas fired or steam heated. The light generates heat due to conversion of electrical power into heat. If Wattage is known, then heat gain can be calculated as,

Q = Total Wattage × use Factor × Allowance Factor

Power equipment:

The power equipments such as fan, motor or any other equipment of this type adds heat in the air conditioned space.Also, the power consumed by the air conditioning fan is converted into heat energy, which is imparted to the air. If the fan is located before the air conditioner, the heat energy must be added to the tota load. If the fan is located after the air conditioner, the heat energy is added to the room sensible heat load.The electric motors used to operate the conditioning equipment within the conditioned spacealso add heat. The power consumed is converted into heat. For example, for electric motor, the heat added is given by,

Q = (Power ratinq of motor in (kW) / Motor efficiency) × Load factor in kW

Where, load factor is the fraction of the total load, at which, the motor is working.

Heat liberated by occupants

Heat gain from occupants is based on average number of people, who are expected to be present in the air conditioned space. Occupants load is very Important factor in cooling load calculations. On an average, human body liberates heat equivalent to heat given away by 200 W bulb. A healthy person in sleep also liberates heat equivalent to 60 W bulb. The heat loss to the surrounding is of main two types:

Sensible heat: This sensible heat loss to the surrounding is due to conduction and radiation, which depends upon difference between body temperature and surrounding temperature.

Latent heat: This latent heat loss to the surrounding is due to evaporation, which depends upon vapour pressure difference between body and surrounding air.

(Video) Calculation of Cooling Load

Thus, heat is thrown by all ways, i.e. conduction, convection and radiation. Evaporation of sweat also contributes to the cool-ng load. The factors affecting occupants load are,

  • Age,
  • Eating habits,
  • Body structure,
  • Activities done by human being.

Latent heat load

The latent heat gain to the space or room to be conditioned may occur due to any or all of thefollowing sources.

  1. Heat gain due to moisture in the outside air entering by infiltration through window cracks and opening doors.
  2. Heat gain due to condensation of moisture from occupants.
  3. Heat gain due to condensation of moisture from any processes such as cooking foods, hot baths or any vaporization carried out in room.
  4. Latent heat gain from products or materials brought into the conditioned space.

The total heat load to be removed by air conditioning and refrigeration will be equal to additionof all the above heat gains i.e. sum of sensible and atent heat loads.Hence, cooling load of various enclosed infrastructures, such as, Cinema hall, Auditorium, Restaurant, Computer lab, MQC lab, MNC lab etc. can be calculated. Generally, split air condtioners are used for a restaurant, MQC lab or MNC lab. The number and size of spit air conditioners to be used depends upon the volume of space to be air conditioned.

Safety Factor Used in Cooling Load Calculation

For designing an air conditioned space, cool-ng load calculations are done for conduction,radiation from wall, occupant’s load, infiltration load, equipment load etc.All these calculations are done on a design day.

A design day is defined as,

  1. A day, when DST and WBT peak simultaneously.
  2. A day, when there is clear sky and there is no haze in air to reduce the solar radiation reaching earth surface.
  3. Internal heat loads being generated within the space are normal.

The calculation of all the heat loads requires many observations and standard tables and formulae to get total heat load. There are always chances of errors in observations and calculations. Therefore, to decide the design load, the total load is multiplied by safety factor. The safety factor usually ranges from 1.05 to 1.1.

Mathematically,

Design load = Safety factor × Total load

Safety factor is also called as factor of safety.

Related Topics

FAQs

What is the purpose of cooling load calculation? ›

The purpose of calculating cooling load is to choose the equipment in the cooling system cycle correctly and economically. If the cooling system elements are selected correctly, the system will work efficiently and for many years in a way that is expected.

What is the purpose of load calculation? ›

A load calculation allows an HVAC technician to determine the size of the system needed to keep the home comfortable in the cooling season. Skilled service technicians use an industry-standard formula to calculate how much cooling power is needed to maintain the environment at an ideal temperature.

How cooling needs are calculated? ›

An overall data center cooling calculation

Because most HVAC systems are sized in tons, we can use the standard conversion equations (watts x 3.41 = BTU/hour) and (BTU/hour / 12,000 = tons of cooling): 76 kW = 880,760 W x 3.41 = 3,003,391.6 BTU/hour. 3,003,391.6 BTU/hour / 12,000 = 250.28 t of max cooling needed.

What factors are considered for cooling load calculation? ›

Managers can calculate the cooling load for each piece of equipment by multiplying either: the number of watts by 3.4 to produce Btu; or volts by amps by 3.4 to produce Btu. Add up all the units' Btu to determine the equipment's total cooling load, and divide the Btu by 12,000 to determine the tons.

What is AC load calculation? ›

The HVAC load calculation shows you the exact amount of BTUs a certain space requires for sufficient heating and cooling. It identifies the square footage of the room to determine the capacity—BTUs per hour—needed to reach the desired indoor temperature.

What is a load calculation? ›

A load calculation is a method of determining the heat gain and loss of a building. Over the years many approaches have been taken. Most contractors, however, have historically referenced the Air Conditioning Contractors of America (ACCA) Manuel J as a basis for residential calculations.

What is load calculation electrical? ›

As mentioned above, the electrical load calculation means adding up the amperage of all your fixtures and appliances. For safety reasons, it is always ideal to build in a margin of safety. Usually, it's best if the load does not exceed 80% of your electrical service capacity.

What is load in HVAC? ›

Load means the amount of heating or cooling required by a building. Capacity refers to the amount of heating or cooling an HVAC system can offer. Thermal loads consider the following factors: Your home's construction and insulation (including walls, floors, and ceilings)

What is cooling load in refrigeration? ›

Cooling load is defined as, “the total heat required to be removed from the space in order to bring it to the desired temperature by air conditioning and refrigeration equipment”.

What is the significance of using Psychrometric calculation in HVAC design? ›

Psychrometrics can be used to predict changes in the environment when the amount of heat and/or moisture in the air changes. Use of psychrometric analysis is also important to determine the volume flow rates of air to be pushed into the ducting system and the sizing of the major system components.

What is total cooling load? ›

The total building cooling load consists of heat transferred through the building envelope (walls, roof, floor, windows, doors etc.) and heat generated by occupants, equipment, and lights. The load due to heat transfer through the envelope is called as external load, while all other loads are called as internal loads.

What is the cooling load of a refrigerator? ›

Cooling load is defined as the average rate at which the heat is removing from the cold space by refrigeration equipment. Similar to the unit of refrigeration it is also expressed in Ton of refrigeration (TR).

Videos

1. HVAC Cooling Load Calculation | HAP Software Tutorial | Part-1 | In Urdu/Hindi
(Tanweer Ahmed)
2. Heat Load Calculation HVAC - Full Explanation Simplified
(HVAC SIMPLIFIED)
3. MANUAL COOLING LOAD CALCULATION USING ASHRAE CLTD/SCL/CLF METHOD (Step by Step guides for beginner)
(Wardi's Way to Go Green)
4. Electric load calculation procedure for Air conditioner management
(EEE Job Care with Jamal)
5. Cooling Load Calculation EXCEL FORM | Load Calculation in HVAC
(Augmintech)
6. #27 Heat Load Part - 4
(Girish Shinde)

Top Articles

Latest Posts

Article information

Author: Allyn Kozey

Last Updated: 12/17/2022

Views: 5842

Rating: 4.2 / 5 (43 voted)

Reviews: 90% of readers found this page helpful

Author information

Name: Allyn Kozey

Birthday: 1993-12-21

Address: Suite 454 40343 Larson Union, Port Melia, TX 16164

Phone: +2456904400762

Job: Investor Administrator

Hobby: Sketching, Puzzles, Pet, Mountaineering, Skydiving, Dowsing, Sports

Introduction: My name is Allyn Kozey, I am a outstanding, colorful, adventurous, encouraging, zealous, tender, helpful person who loves writing and wants to share my knowledge and understanding with you.